Energy Recovery (ERV/HRV): Efficiency, Savings, Air States
How to calculate energy recovery savings in HVAC: temperature effectiveness, air states on the psychrometric chart, plate vs. wheel, and standards.
Energy recovery (HRV/ERV) is the transfer of thermal energy from the exhaust air to the supply air through a heat exchanger. The temperature effectiveness is calculated as , where is the supply-air temperature before the exchanger, after the exchanger, and the exhaust-air temperature.
Why energy recovery gets specified
In US practice the driver is ASHRAE Standard 90.1 — and the IECC, which references it — whose energy-recovery requirements attach to a system based on its supply airflow and its outdoor-air fraction. The thresholds move with climate zone and with the edition in force, so check the version your jurisdiction has actually adopted rather than a remembered number. AHRI Standard 1060 governs how the performance of the exchanger itself is rated and certified.
Types of energy-recovery exchanger
Plate exchanger (cross-flow or counter-flow)
The air streams are separated by metal or plastic plates, so no moisture is transferred, only sensible heat. Temperature effectiveness runs roughly 50–70% for the cross-flow arrangement and 80–93% for counter-flow. Plates are cheap, simple to maintain and carry no odor across; the trade-off is that below about 23°F supply-air temperature they need a defrost bypass, and condensate forms on the exhaust-air side.
Enthalpy wheel (rotary)
A rotor of sorption (desiccant) material rotates (5–10 rpm) between the supply and exhaust streams, so it transfers both heat and moisture. Overall (enthalpy) effectiveness is 75–85%, and the moisture transfer reduces the need for winter humidification. The downsides are odor carry-over (up to 5%) and higher cost, though frosting is less of a problem than with plates.
Run-around coil (glycol/water loop)
Two heat exchangers linked by pipework with a glycol loop; the air streams never come into contact. Effectiveness is only 40–60% and a pump is needed, but the full separation of the streams suits odorous or hygienically sensitive applications.
Energy-recovery calculation
Temperature effectiveness (sensible)
Example (winter):
- °F (outdoor air)
- °F (exhaust air from the room)
The air entering the heating coil is 56.5°F instead of 10°F — that is the whole preheat load the coil no longer has to carry.
Recovered heating capacity
Example: CFM → 175,800 Btu/h (14.6 tons of heating)
Annual energy savings
where = the annual number of operating hours during the heating season — commonly 3,000–4,500 h/year for a heating-dominated climate, though the honest number comes from bin data for the actual site.
Example: 615 MMBtu/year
Energy recovery on the psychrometric chart
The psychrometric chart in its US (Carrier) layout puts dry-bulb on the horizontal axis; PsychroView renders air states in either this or the European Mollier view.
Plate exchanger (no moisture transfer)
Supply air: a horizontal shift to the right (constant ) from point 1 (outdoor air) toward the exhaust-air temperature.
Exhaust air: a horizontal shift to the left — condensation on the fins is possible below the dew point of the exhaust air. Both shifts can be checked with a pencil on a blank chart to print — with energy recovery the graphical check is the quickest, because a nonsensical slope shows up before an error in a table does.
Enthalpy wheel (with moisture transfer)
Supply air: a diagonal shift — both and increase (moisture is added from the exhaust air).
Condensation and frost control in energy recovery
In winter, moisture from the exhaust air condenses on the cold fins — a condensate drain is required (trap, discharge to the sanitary drain).
At outdoor temperatures below roughly 23°F (depending on the state of the exhaust air), the condensate can freeze on the fins. Solutions:
- Exhaust-air bypass — part of the exhaust air is routed around the exchanger, raising the fin temperature
- Electric preheat of the supply air — preheating upstream of the exchanger
- Enthalpy wheel — inherently more resistant thanks to rotation (mechanical defrosting)
Practical selection guidance
| Application | Recommendation |
|---|---|
| Single-family home, apartment | Counter-flow plate (η > 85%) |
| Office, school, hotel | Plate or wheel |
| Restaurant (odors) | Run-around coil or plate with an air gap |
| Large production building | Wheel (high flow rates, significant moisture load) |
| Hospital, cleanroom | Plate (no transfer between the air streams) |
Standards and regulations
- ASHRAE Standard 90.1 — energy standard for buildings, energy-recovery requirements
- AHRI Standard 1060 — performance rating of air-to-air exchangers for energy recovery ventilation
- ASHRAE Standard 84 — method of test for air-to-air heat/energy exchangers
- EN 308 (European standard) — heat exchangers, methods for performance testing
Try PsychroView for free
Interactive psychrometric chart directly in the browser. No registration required.
Open app →Or browse example projects to see real HVAC calculations.
Keywords: energy recovery ventilator, HRV efficiency calculation, heat recovery calculation, plate heat exchanger, sensible heat recovery