Cooling Coil in an AHU: Capacity and Dehumidification Calculation
How to size a cooling coil in an air handling unit. Calculating cooling capacity, dehumidification, dew point and the air state after the coil.
The cooling coil in an air handling unit (AHU) cools the supply air below its dew point — condensing out the excess moisture and draining it away as condensate. The total cooling capacity is the sum of the sensible and latent heat: , where and are the air enthalpies before and after the coil.
The principle of cooling with dehumidification
The air enters the coil at temperature and relative humidity . The coil cools it through the dew point () to the outlet temperature :
- Sensible cooling — a drop in temperature with no change in humidity, until the air reaches its dew point
- Latent cooling (dehumidification) — below the dew point the water vapor condenses, and the humidity ratio falls
- Outlet state — the air leaves the coil saturated () or is subsequently reheated to the required temperature
The principle of cooling without dehumidification
If the outlet temperature stays above the dew-point temperature, no condensation occurs — the air is merely cooled.
- Sensible cooling — a drop in temperature with no change in humidity, until the air reaches its dew point
- Outlet state — the air leaves the coil more saturated than at the inlet
Calculating the cooling capacity
Total cooling capacity
with in CFM and enthalpies in Btu/lb. The constant 4.5 is 60 min/h × 0.075 lb/ft³ — recompute it at altitude.
The sensible component
The latent component (dehumidification)
Condensate flow
Divide by 8.34 lb/gal for gallons per hour — the number that sizes the drain pan and trap.
A worked example
Given: an AHU at 1,800 CFM, coil inlet: = 90°F, = 55%, outlet: = 57°F, = 95%.
Psychrometric values:
- Air density at inlet:
- (90°F, φ 55%):
- (57°F, φ 95%):
- ,
Results:
- Total capacity: (10.9 tons)
- Sensible capacity:
- Latent capacity:
- Condensate: — about 7.1 gal/h
Sensible heat ratio (SHR)
The SHR (Sensible Heat Ratio) gives the share of the total cooling capacity that is sensible cooling:
Typical values:
- Offices: SHR = 0.75–0.85 (low internal latent-heat production)
- Restaurants, natatoriums: SHR = 0.45–0.65
- Hot, humid climates: SHR = 0.50–0.65
An SHR this far below the office range is the signature of a hot, humid design day — over half the coil duty is going into moisture removal, not temperature.
The temperature after the coil (bypass factor)
A real coil never cools all the air exactly to the surface temperature of the exchanger. The bypass factor (BF) = the fraction of air that passes through the coil without contact:
where is the apparatus dew point temperature — the effective surface temperature of the exchanger.
The BF for a finned exchanger is typically 0.05–0.15. On the psychrometric chart, the outlet-air state lies on the line connecting the state , with the saturation curve — the distance corresponds to the BF.
Cooling on the psychrometric chart
On the chart:
- Plot the inlet air state (point 1)
- Draw the coil process line down and to the left toward the saturation curve — point 2’ is the ideal outlet at the ADP (BF = 0)
- The actual outlet (point 2) lies on the segment 1–2’ at a distance BF from the saturation curve
You can also work the construction through by hand — a blank chart to print draws the saturation curve at 0.5 mm, so it is easy to aim at with a ruler. PsychroView performs this calculation automatically once you enter the inlet state and the outlet temperature or enthalpy.
Frequently asked questions
How do I find the cooling capacity I need? The cooling capacity is set by the room’s heat gains (sun, people, lighting, equipment) plus the heat brought in by ventilation. For a standard office, reckon on roughly 19–32 Btu/h per square foot of total cooling capacity — the familiar 375 to 630 square feet per ton.
Why is the coil outlet saturated air? The coil cools the air below its dew point — moisture condenses and the air approaches saturation. Downstream of the coil the air is typically φ = 90–100% and relatively cold (54–61°F), which is why a reheat coil is usually placed after it.
What is a chilled-water coil and a DX coil? Chilled-water coil (CW) — cold water (typically 43/54°F supply/return) from a central cooling source (a chiller) flows through the tubes. DX coil (direct expansion) — refrigerant evaporates in the coil directly from a compressor unit.
Try PsychroView for free
Interactive psychrometric chart directly in the browser. No registration required.
Open app →Or browse example projects to see real HVAC calculations.
Keywords: cooling coil sizing, cooling coil capacity, air dehumidification, HVAC cooling coil, SHR calculation